								Analysis of Partial Discharge Patterns for Generator Stator Windings
								
									
										
											
											
												Tae-Sik Kong,
											
										
											
											
												Hee-Dong Kim,
											
										
											
											
												Tae-Sung Park,
											
										
											
											
												Kyeong-Yeol Kim,
											
										
											
											
												Ho-Yol Kim
											
										
									
								 
								
									
										Issue:
										Volume 4, Issue 2, March 2015
									
									
										Pages:
										17-22
									
								 
								
									Received:
										16 February 2015
									
									Accepted:
										4 March 2015
									
									Published:
										12 March 2015
									
								 
								
								
								
									
									
										Abstract: Forced outage of generators due to stator winding insulation failure can result in significant financial loss because of the high cost repair and loss of production. In recent years, the demand for insulation diagnosis is increasing to prevent unexpected failures, as the capacity of generators has increased. Insulation diagnosis is composed of the insulation resistance measurement, polarization index measurement, dissipation factor (DF) tip-up test, AC current increasing ratio measurement, and the partial discharge (PD) measurement. In this paper, the results of the PD measurement and PD pulse pattern analysis performed on a healthy generator and two generators that experienced dielectric breakdown failure during operation is presented.
										Abstract: Forced outage of generators due to stator winding insulation failure can result in significant financial loss because of the high cost repair and loss of production. In recent years, the demand for insulation diagnosis is increasing to prevent unexpected failures, as the capacity of generators has increased. Insulation diagnosis is composed of the ...